| Features |
Description |
| Product Type |
True Online Double-Conversion UPS |
| Series |
UNITEC X4 Series |
| Output Power Capacity |
3000 VA / 2700 W |
| Phase |
Single Phase + Ground |
| Power Factor |
0.9 |
| Topology |
True Online Double Conversion |
| Waveform Type |
Pure Sine Wave |
| Nominal Output Voltage |
200/208/220/230/240 VAC |
| Output Voltage Regulation |
±2% |
| Output Frequency |
50/60 Hz, Synchronized to Mains |
| Battery Mode Frequency |
50/60 Hz ±0.02 Hz |
| Input Voltage |
200/208/220/230/240 VAC |
| Input Voltage Range |
110-290 V |
| Input Frequency |
50-60 Hz, Auto-Detect |
| Input Power Factor |
>0.98 |
| Input THDi |
<7% at 100% Non-Linear Load |
| Generator Input |
Supported |
| Crest Factor |
3:1 |
| Efficiency |
AC Mode: Up to 90%; Battery Mode: >88%; ECO Mode: >94% |
| BATTERY |
Description |
| Battery Type |
Lead-Acid |
| Battery Voltage |
72 VDC |
| Battery Capacity |
12 V / 9 Ah |
| Recharge Time |
4-5 Hours to 90% Capacity |
| Charging Current |
1.4 A |
| Backup Time |
Approx. 5 Minutes at Full Load; 15-30 Minutes Depending on Load |
| External Battery Connection |
Anderson-Style PowerPole Modular Connector |
| Hot-Swappable Battery |
Supported |
| PROTECTION & FEATURES |
Description |
| Overload Protection |
Supported |
| Short-Circuit Protection |
Supported |
| Overheat Protection |
Supported |
| Low Battery Protection |
Supported |
| Self-Diagnostics |
Supported |
| Emergency Power Off |
EPO Supported |
| Advanced Battery Management |
Supported |
| Surge & Lightning Protection |
Built-In |
| Cold Start |
Supported |
| ECO Mode |
Supported |
| Transfer Time |
Utility to Battery: 0 ms; Utility to Bypass: <4 ms |
| CONNECTIONS & MANAGEMENT |
Description |
| Input Connection |
IEC320 C14-10A |
| Output Connections |
6 x Universal Output + 1 x IEC320 C19-16A |
| Communication Interfaces |
Smart RS232, USB, SNMP Slot, and RJ45 |
| LCD Display |
Load, Battery, Input, Output, and Operating Mode Information |
| Operating System Support |
Windows, Linux, and FreeBSD |
| Rack / Tower Installation |
Rack and Tower Convertible |
| GENERAL |
Description |
| Dimensions |
440 mm x 86.5 mm x 600 mm |
| Rack Height |
2U |
| Weight |
Approx. 26.2 kg |
| Operating Temperature |
0°C to 40°C |
| Storage Temperature |
-25°C to 55°C |
| Operating Humidity |
0% to 90% RH, non-condensing |
| Operating Altitude |
<1500 m, Derating Above 1500 m |
| Noise Level |
<50 dB at 1 m |
| Warranty |
2 Years Onsite |
Note: The UNITEC X4-3000-RT is a 3000 VA / 2700 W True Online Double-Conversion UPS featuring Pure Sine Wave output and a 0.9 power factor. It is designed to provide stable and reliable power protection for servers, network equipment, workstations, and other critical applications.
Important: The X4-3000-RT supports Rack/Tower installation, ECO Mode, generator input, hot-swappable battery replacement, EPO, external battery connection, and multiple communication interfaces including RS232, USB, SNMP, and RJ45.