ZIRCON รุ่น ZC-MP 6kVA
คุณสมบัติ
- เครื่องสำรองไฟ 6kVA
- เทคโนโลยีขั้นสูงสุดแบบ True Online Double Conversion
- ความถี่สูง, TOWER DESIGN
- PF 0.9, LCD&LED, EPO, etc.
- 1 phase In, 1 phase Out
*** ผู้รับเหมาโครงการต้องการราคาพิเศษสนใจติดต่อ ***
เบอร์มือถือ : 063-1963553 ไอดีไลน์ : ifocusshop
ZC-MP
Input | Phase Rated Voltage Voltage Range Frequency Range Power Factor Current THDi Bypass Voltage RangeECO Range Hamonic Current |
Single phase & Ground 220/230VAC +/- 25% 140-290V* 40Hz-70Hz (settable) +/- 0.1% >0.99 5% at 100% non-linear load Max, voltage; +5% (optional +5%, +10%, +25%) Min. voltage:-45% (oplional -20%,-30%, -45%) Frequency protection range: +/-10% same as the bypass <5% ( 100% non-linear load ) |
Output | Phase Rated Voltage Power Factor Voltage Regulation Frequency – Utility Mode – Battery Mode Crest Factor THDWave Form |
Single phase & Ground 220/230VAC 0.9 +/- 1% 1%,2%,4%,5%,10% of the rated frequency (optional) 50Hz +/- 0.1% Hz 3:1 < 2% with Linear Load < 5% with non Linear Load Pure Sine Wave |
Efficiency | AC Mode (full load) Battery Mode (full load) ECO Mode (tull load) |
Up to 90% >88% >94% |
Battery | Voltage Capacity (Standard unit) Backup Time Recharge Time to 90% Charging Current -Standard Battery Number Battery Socket |
192/216/240 Vdc 12V/9Ah 15-30 min (Depend on load), Estimated remaining time display on the LCD 4-6 Hours 1A (S), 6A (H) 16/18/20 pcs (Settable) Anderson Like PowerPole Modular Connectors |
Transfer Time | Utility to Battery; 0ms, Utility to Bypass <4ms | |
Protection | Overload – AC Mode
– Batt. Mode |
108%+/-5%<Load<150%+/-5% exceed 30s, cut off and alarm, 150%+/-5%<Load<200%+/-5% exceed 300ms, cut off and alarm 108%+/-5%<Load<150%+/-5% exceed 30s, tranfer to bypass and alarm, 150%+/-5%<Load<200%+/-5% exceed 300ms, tranfer to bypass and alarm” Load <100%-150%; 30S; Load >150%; 300ms then shutdown UPS completely Load >130%; 60S then shutdown output Hold Whole System Line mode; Switch to Bypass; Battery Mode, shutdown UPS immediately Alarm and Switch off Upon Power On and Software Control Shutdown UPS immediately Advanced Battery Management Compiles with EN962040-2 |
ALARM | Audible & Visual | Line Failure, Battery Low, Overload, System Fault |
Display | Status LED & LCD Reading on the LCD |
Load/Battery/Input/Output/Operating Mode information Load/Battery/Input/Output/Operating Mode information |
Physical | Dimension(WxHxD) mm Weight (kg) Input Connection Output Connection External Battery Connection |
250 x 655 x 590 70kg hardwired hardwired Anderson like PowerPole Modular connectors |
Communication Interface |
Smart RS232/USB Port Communication Slot R.J45 |
Support Windows Family, Linux, FreeDSB, etc. SNMP Card (independent to RS232) Built-in Power Surge, Lightning Protection Device |
Environment | Operating Temperature Storage Temperature Humidity Altitude Noise |
0 °C – 40 ° C -25 °C – 55 °C 0-95% (Non-condensing) <1500 m. (derating while > 1500m) <55 dB (at 1 meter) |
Safety Conformance | CE | |
Industry Standard | Safety EMI EMS Surge ISO |
Meet IEC62040-1 GB4943 IEC 62040-2 IEC 62040-2 Meeting IEC62040-1 1.2/50uS-8/20uS 6kV/3kA 9001 : 2015 , 14001 : 2015 |
You must be logged in to post a review.